SH15 Amorf qotishmali moyli transformator
- 6 / 6.3 / 10 kV → 0.4 kV
- 30 – 2500 kVA
S13-M germetik moyli taqsimlovchi transformator, 30–2500 kVA, 6/6.3/10 kV dan 0.4 kV ga, past salt yurish yoʻqotishlari va shovqin.
S13 — Jiangsu Xinhong kompaniyasi tomonidan avvalgi S11 seriyasi asosida ishlab chiqilgan taqsimlovchi transformator. Yangi materiallar va yangi texnologik jarayonlarni qoʻllash orqali salt yurish yoʻqotishlari va shovqinni kamaytirish maqsadida oʻzak va chulgʻamlar konstruksiyasi optimallashtirilib, qayta loyihalangan.
Shovqin darajasi JB/T 10088-2016 tarmoq standarti meʼyorlaridan oʻrtacha 20% past.
| Model | Nominal quvvat (kVA) | Chulgʻamlarni ulash guruhi | YuK (kV) | Rostlash diapazoni (PBV) | PK (kV) | Salt yurish yoʻqotishlari (Vt) | Qisqa tutashuv yoʻqotishlari Dy (Vt) | Qisqa tutashuv yoʻqotishlari Yy (Vt) | Salt yurish toki (%) | Qisqa tutashuv kuchlanishi uk (%) |
|---|---|---|---|---|---|---|---|---|---|---|
| S13-M-30 | 30 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 80 | 630 | 600 | 1.5 | 4 |
| S13-M-50 | 50 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 100 | 910 | 870 | 1.3 | 4 |
| S13-M-63 | 63 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 110 | 1090 | 1040 | 1.2 | 4 |
| S13-M-80 | 80 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 130 | 1310 | 1250 | 1.2 | 4 |
| S13-M-100 | 100 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 150 | 1580 | 1500 | 1.1 | 4 |
| S13-M-125 | 125 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 170 | 1890 | 1800 | 1.1 | 4 |
| S13-M-160 | 160 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 200 | 2310 | 2200 | 1 | 4 |
| S13-M-200 | 200 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 240 | 2730 | 2600 | 1 | 4 |
| S13-M-250 | 250 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 290 | 3200 | 3050 | 0.9 | 4 |
| S13-M-315 | 315 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 340 | 3830 | 3650 | 0.9 | 4 |
| S13-M-400 | 400 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 410 | 4520 | 4300 | 0.8 | 4 |
| S13-M-500 | 500 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 480 | 5410 | 5150 | 0.8 | 4 |
| S13-M-630 | 630 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 570 | 6200 | 6200 | 0.6 | 4.5 |
| S13-M-800 | 800 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 700 | 7500 | 7500 | 0.6 | 4.5 |
| S13-M-1000 | 1000 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 830 | 10300 | 10300 | 0.6 | 4.5 |
| S13-M-1250 | 1250 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 970 | 12000 | 12000 | 0.5 | 4.5 |
| S13-M-1600 | 1600 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 1170 | 14500 | 14500 | 0.5 | 4.5 |
| S13-M-2000 | 2000 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 1550 | 18300 | 18300 | 0.4 | 5 |
| S13-M-2500 | 2500 | Yyn0 yoki Dyn11 | 10 / 6.3 / 6 | ±5% yoki ±2×2.5% | 0.4 | 1830 | 21200 | 21200 | 0.4 | 5 |
Chulgʻamlarni ulash guruhi Yyn0 yoki Dyn11, YuK 10 / 6.3 / 6 kV, rostlash diapazoni ±5% yoki ±2×2.5% va PK 0.4 kV barcha 19 nominal quvvat uchun amal qiladi. Qisqa tutashuv kuchlanishi: 30–500 kVA uchun 4%, 630–1600 kVA uchun 4.5%, 2000–2500 kVA uchun 5%. 630 kVA va undan yuqori quvvatlarda Dy va Yy ulanishlari uchun qisqa tutashuv yoʻqotishlarining bitta qiymati amal qiladi.
Parametrlar 50 Gts chastotali standart konstruksiyalarga tegishli. Boshqa quvvatlar, kuchlanish kombinatsiyalari, chulgʻamlarni ulash guruhlari va maxsus ijrolar soʻrov boʻyicha taqdim etiladi. Qiymatlar oldindan ogohlantirmasdan yangilanishi mumkin — iltimos, ularni texnik taklifda aniqlashtiring.
Kerakli quvvat, kuchlanish va miqdorni yuboring — biz Oʻzbekistonga yetkazib berishni oʻz ichiga olgan texnik-tijorat taklifi bilan javob beramiz.