S13 Oil-immersed distribution transformer
- 6 / 6.3 / 10 kV → 0.4 kV
- 30 – 2500 kVA
The TMG-400 (factory model S13-M-400) is a 400 kVA hermetic oil-immersed 10 (6) / 0.4 kV distribution transformer that typically supplies an apartment building, supermarket or small factory. Key figures: LV rated current 577 A, up to 360 kW at cos φ 0.9, no-load loss 410 W. Price and a techno-commercial offer are sent on request within 24 hours.
| Model | S13-M-400 / TMG-400/10/0.4 |
|---|---|
| Rated capacity | 400 kVA |
| HV voltage | 10 / 6.3 / 6 kV |
| LV voltage | 0.4 kV |
| Vector group | Yyn0 or Dyn11 |
| Tapping range (off-circuit tap changer) | ±5% or ±2×2.5% |
| No-load loss | 410 W |
| Load loss (Dy / Yy) | 4520 / 4300 W |
| No-load current | 0.8 % |
| Short-circuit impedance | 4 % |
| Frequency | 50 Hz |
| Cooling | ONAN |
| Design | Hermetically sealed corrugated tank, mineral oil |
| Standards | GB/T 1094 (IEC 60076), GB/T 6451, JB/T 10088 |
| HV rated current at 10 kV | 23.1 A |
|---|---|
| HV rated current at 6 kV | 38.5 A |
| LV rated current at 0.4 kV | 577 A |
| Active power at cos φ = 0.8 / 0.9 / 0.95 | 320 / 360 / 380 kW |
| Recommended continuous load (70–80 % loading, cos φ = 0.9) | 252–288 kW |
| Three-phase short-circuit current at the 0.4 kV terminals (approx.) | 14.4 kA |
Rated current is calculated as I = S / (√3 · U). The short-circuit current is taken as the LV rated current divided by uk, neglecting the supply network impedance. Network and cable impedance lower the actual current, while the uk tolerance (±10 %) and the IEC 60909 voltage factor can raise it by roughly 10 %, so select the breaking capacity of circuit breakers from the short-circuit calculation of the project.
The amorphous-alloy core of the SH15 cuts the no-load loss by 51 % compared with the S13. For one 400 kVA transformer this saves about 1840 kWh per year, because no-load loss is present the whole time the transformer is energised, regardless of the load.
| Parameter | S13-M-400 | SH15-M-400 (amorphous) |
|---|---|---|
| No-load loss | 410 W | 200 W |
| Annual no-load energy loss (8760 h) | 3592 kWh | 1752 kWh |
| Load loss (Dy) | 4520 W | 4520 W |
| No-load current | 0.8 % | 0.5 % |
| Efficiency at 50 % load, cos φ = 0.9 | 99.15 % | 99.27 % |
| Efficiency at 100 % load, cos φ = 0.9 | 98.65 % | 98.71 % |
| Vector group | Yyn0 or Dyn11 | Dyn11 (Yyn0 on request) |
Efficiency is calculated from the catalogue losses: η = P / (P + P₀ + β²·Pk), where P = β·S·cos φ is the output active power and β is the load factor.
400 kVA is a commonly requested rating for medium-sized loads. Typically, the TMG-400 is installed in substations serving residential complexes and multi-storey housing, supermarkets and smaller shopping centres, and small and medium factories, workshops and warehouses. At this size one unit usually covers the lighting, lifts, pumps, ventilation and refrigeration of a single site. The hermetically sealed corrugated tank with vacuum oil filling allows the transformer to be placed both in indoor substations and in outdoor compact substations.
Size the transformer on the calculated maximum demand after applying a diversity factor. A continuous loading of 70–80% is a sound target for an oil-immersed unit: for the TMG-400 that is 252–288 kW at cos φ 0.9, against 360 kW at full load. If the demand with margin fits within 250 kVA and no growth is planned, the TMG-250 with its lower no-load loss is the leaner choice. If the load is already close to 288 kW, or a second construction phase or a new production line is planned, move up to the TMG-630 or design a substation with two TMG-400 units for redundancy.
The TMG-400 is built with vector group Yyn0 or Dyn11. Dyn11 copes better with unbalanced single-phase loads and with third harmonics from LED lighting, UPS systems and IT equipment, and it gives a larger single-phase fault current, so protection on outgoing feeders operates more reliably. For housing and retail with a high share of single-phase consumers it is typically the preferred option. Yyn0 remains the traditional choice where the neutral is lightly loaded, for example with a mainly three-phase motor load. Note that for the S13-M-400 the load loss depends on the connection: 4520 W for Dy and 4300 W for Yy.
Choose the loss level by load profile. No-load loss is incurred all 8760 hours a year regardless of load, so at low average loading (housing with night-time and off-season lulls, warehouses, seasonal sites) the amorphous SH15-M-400 is the better fit: 200 W no-load loss instead of 410 W, 51% less, with the same 4520 W load loss as the Dyn11 S13-M-400 (SH15 is Dyn11 as standard; with a three-phase three-limb core, Yyn0 can be supplied on request, so state it in your inquiry if needed). The S22-M-NX1 has lower losses than S13, meets energy-efficiency grade 1 to GB 20052-2020 and holds a type-test certificate at 400 kVA, so it suits tenders requiring either. A steady, high load suits the S13-M-400, or the S22-M-NX1 where lower total losses matter more.
The 400 kVA transformer is also supplied as part of a compact substation: ZGS American-type pad-mounted substation (KTPN), up to 1600 kVA, or YB European-type substation (BKTP / GKTP), up to 2500 kVA. The substation is assembled and tested at the factory, so the site work mainly comes down to setting it in place and connecting the cables.
The 400 kVA TMG-400 (S13-M-400) has an LV rated current of 577 A at 0.4 kV. On the HV side the rated current is 23.1 A at 10 kV and 38.5 A at 6 kV. The three-phase short-circuit current at the LV terminals is about 14.4 kA at the nominal uk of 4% and an infinite supply. The ±10% uk tolerance and the IEC 60909 voltage factor can raise the real maximum by roughly 10%, while the impedance of the supply network and cables lowers it, so confirm the breaking capacity of the LV breaker with the project short-circuit calculation (or choose it with margin above 14.4 kA).
At full load the 400 kVA TMG-400 (S13-M-400) delivers 360 kW at cos φ 0.9, 320 kW at cos φ 0.8 and 380 kW at cos φ 0.95. For continuous operation with headroom, a loading of 70–80% is recommended, which is 252–288 kW at cos φ 0.9. If the calculated demand is higher or growth is expected, consider the TMG-630 instead.
The price of the TMG-400 (S13-M-400) is quoted on request only. It depends on the HV voltage, vector group, loss level (S13, amorphous SH15 or energy-efficient S22-M-NX1), options, scope of supply and delivery terms (FOB, CIF or DAP Tashkent). LALOGO sends a techno-commercial offer within 24 hours (one business day) of a request made via the form, sales@lalogo.uz, Telegram or WhatsApp.
Production of the TMG-400 (S13-M-400) takes 20–35 days after advance payment; delivery to Tashkent by rail or road via Khorgos / Alashankou and Kazakhstan usually takes 15–25 days. Each unit ships with a routine test report, passport and operation manual in Russian and English, drawings, packing list and certificate of origin. A statement of compliance with GOST / O‘zDSt is prepared on request.
A 400 kVA transformer usually covers an entire site on its own (an apartment building with lifts and pumps, a supermarket or a small factory): at a normal 70–80% loading the TMG-400 (S13-M-400) delivers 252–288 kW at cos φ 0.9. The TMG-400 fits pad-mounted and prefabricated compact substations, and where critical loads need redundancy the substation is built with two TMG-400 units. If the load with margin fits within 250 kVA, the TMG-250 is leaner; above 288 kW, move to the TMG-630.
At 400 kVA a type-test certificate is held by the energy-efficient S22-M-NX1 version, which meets energy-efficiency grade 1 to GB 20052-2020; the standard TMG-400 (S13-M-400) has no type-test certificate. If a tender or project requires type tests, we offer the S22-M-NX1 in place of the TMG-400. Every unit, whatever the series, ships with a routine test report, and the manufacturer's management systems are certified to ISO 9001, ISO 14001 and ISO 45001.
Send us the HV voltage, vector group, number of TMG-400 units and delivery point, and we will prepare a techno-commercial offer within 24 hours.